HOME  DEALERS  ABOUT US  CONTACT
 PRODUCTS  NEWS  EVENTS  STORE
No G310A-A
February 20, 2007

Guardian Model G300-A
Owner's / Installation Manual

Page 15


AIMING NOZZLES

AIMING THE SPRAY NOZZLES AND PLACEMENT OF TEMPERATURE SENSORS
  1. Locate the centerline of the magnetic base nozzle assemblies directly overthe burner centerline (front to back) as illustrated in FIGURE 23. If needed, the magnetic assemblies can be placed up to 5" inside the burner centerline to the inside of the hood. The magnetic bases are also to be between 1" Min. and 2" Max. back from the inside of the hood hip of the range hood. (See FIGURES 23 & 25)
  2. Using a 1" box end wrench and a crescent wrench loosen the locking nut on the adjustable ball fitting a point 1/2 way between the center of the front and back burners.
 

Each nozzle shall be aimed at the respective center point along the burner centerline, between the front and back burner. (Left nozzle -left aim point; right nozzle right aim point.) To adjust the nozzles see FIGURE 24 & 25. Be sure to re-tighten the locking nut after aiming is completed, being careful not to change nozzle positions from the correct aim point.

3. After retightening the swivel locking nut of each nozzle, recheck nozzles are aimed correctly.

4. Attach the temperature sensors to the side of each Magnetic nozzle base, with the diodes pointed downward towards the stove top.

                  

FIGURE 24

TARGET AREA FOR SPRAY NOZZLES

                                    

                                    

FIGURE 25


page 15 of 18   previous << 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 >> next