STEP 6 (Extinguisher Kit Mounting)
Insert the extinguisher and bracket kit in the desired location at the rear of the kitchen cabinet (left or right side). Attach with the mounting screws provided (Figure 9).
NOTE: Make sure the ball bearing wheel, cable guide and micro switch have been properly positioned to match up with the rear corner pulley assembly (left or right side mounting).
Spacer tabs are provided for proper positioning of the extinguisher bracket for cabinets with or without top or bottom header boards.
NOTE: The ball bearing wheel, cable guide and/or micro switch may be located on either the left or right side of the mounting bracket for ease of installation.
FIGURE 9
STEP 7 (Detection Kit Adjustments)
Place the looped end of the detection kit cable on the hook of the cable tension adjuster through Hole C (See Figure 9). Use an S-hook if necessary and make sure the turnbuckle is fully extended.
Adjust the detection kit chain between the two front fusible links so that the links are in the proper position (Figure 6 and Figure 12). After final adjustments have been made, excess chain should be removed.
Pull excess cable through the cable nut until all slack is removed and secure tightly with the set screw (See Figure 10). Make sure the fire detectors (fusible or reusable links) align according to Figures 6 and 12. If necessary, you may use extra S-hooks to adjust proper spacing, however, no more than two (2) S-hooks may be connected consecutively.
NOTE: When extra S-hooks are installed, they should be crimped tightly closed with pliers.
|