ELECTRIC: Electrical Contactor:1 20-volt coil AC operation for electric range 50 AMP (resistive), 2-pole type. (P/N 21C/KB54-3) Contactor Enclosure: Protective cover for 120-volt electric contactors. (P/N 21C/KB71)
For additional electric shutoffs see Addendum No. 71758-3 dated August 2000.
FIGURE 14
WIRING INSTRUCTIONS:
Instructions for wiring the required range top shut-off device and other electrically operated accessories are provided separately with each component. The micro switch (P/N PCLCD-2A) is factory installed on the mounting bracket. A conduit attachment hole for a 1/2" conduit fitting is provided for 120volt wiring (see Figure 2). Micro switch wire leads are provided as follows (see Figure 15):
Red - Common connection, usually connected to electric power source.
Brown - Normally closed, provides continuous electric current until the Guardian system is activated, at which time power is switched "off" from connected accessories.
Black - Normally open, no electric current will flow until the Guardian system is activated, at which time power is switched "on" to connected accessories.
Maximum electrical load rating for the micro switch is 21 AMP, 1 H.P. at 125-volt AC. Consult your TFC representative for specific wiring instructions. |
FIGURE 15
WIRING DIAGRAMS
Wiring diagrams are provided as a guide to installing fuel shutoffs. All fuel shut-offs should be installed in accordance with the regulations and codes which apply in your locality.
|