OPTIONAL MODEL 1384-ASH EXTINGUISHER SYSTEM
STOVE TOPS WITH MORE THAN 26 1/2" FROM
HOODS / NOZZLES

The following applications and limitations apply to extinguisher systems identified as Model 1 384-ASH for installation in unusually high range hoods (where the distance from the fire detection links to the kitchen range top cooking surfaces exceeds 26 1/2 inches). Systems installed in accordance with these instructions must also comply with all other applications and limitations as listed in the owner's manual No. 71758 for Model 1384-A Extinguisher System.

 

FIRE DETECTION LINKS: For gas operated ranges, only 280 F fusible links (P/N FLINK-G280) or 280 F reusable links (P/N RLINK-5734) can be used. For electrically operated ranges, only 212 F fusible links (P/N FLINK-E212) or 220 F reusable links (P/N RLINK-5730) can be used.

INSTALLATION LIMITATIONS: The distance from the appliance nozzles to the range top surface shall not exceed 30 inches (21 3/4 " minimum). The distance from the fire detection links to the kitchen range top cooking surface elements shall not exceed 31 1/2" (23 3/4" minimum).