HOME  DEALERS  ABOUT US  CONTACT
 PRODUCTS  NEWS  EVENTS  STORE
No G310A-A
AUGUST 1, 2000

Guardian Model G300-A
Owner's / Installation Manual

Page 16


TROUBLESHOOTING GUIDE

CAUTION: DURING CHECK OUT PROCEDURES MAKE SURE SAFETY PULL PIN IS INSTALLED.

CPU Board

Continuous Alarm
Check the following: (See FIGURE 3)


- Terminals are tight on P1 terminal strip.

- Sensor cable wires are not shorted or frayed.

- Open or bad connection to solenoid release valve.

- Replace one sensor at a time.

Solenoid I Mechanical Valve

No Activation

Check the following: (See FIGURE 3)

- Terminals are tight on P1-8 & 9.

- Verify the red wire goes to P1-8 and the black wire goes to P1-9.

- Use a Multimeter to measure the signal on P1-8 (+) and P1-9 (-) during system checkout. See "Auxiliary and Solenoid Release Valve" section for instructions. If signal does not appear, replace CPU board. If indication of signal exist perform next step.

- Disconnect wires from P1-8 & P1-9. Use a 9-volt battery and place the red wire on positive and the black wire on negative. If solenoid DOES NOT ACTIVATE use a Multimeter to measure the resistance between the two wires. The resistance should be approximately 190 ohms. If no resistance, replace solenoid.

Electric Shutoff

Check the following:

Visual Check
Verify the configuration and determine if the electric shutoff is Sonic or Non-sonic or if it is 3 Prong, 4 Prong or Hardwired

No Power:

- Verify power is getting to stove by turning on burner. If no power, disconnect electric shutoff and plug stove directly into the wall.


- If power to stove exist plugging directly into wall, replace electric shutoff.

- For hardwired versions, have an electrician verify power is supplied to stove through electric shutoff.
Sonic

No Sonic Activation
Verify db level (loudness) is adequate by opening cabinet doors and moving stove away from wall. If electric shutoff does not activate, replace shutoff. If electric shutoff activates, installation of a remote alarm may be necessary to compensate for the type of cabinet.

Non-Sonic

No Activation
Verify that wires are connected correctly and the termination points on the CPU bard and electric shutoff printed circuit board are not loose. If connections are good, verify auxiliary output.

Gas Shutoff

Sonic

No activation
Verify db level (loudness) is adequate by opening cabinet doors and moving stove away from wall. If gas shutoff does not activate, replace shutoff. If gas shutoff activates, installation of a remote alarm may be necessary to compensate for the type of cabinet.

Non-Sonic

No Activation
Verify that wires are connected correctly and the termination points on the CPU bard and electric shutoff printed circuit board are not loose. If connections are good, verify auxiliary output.


page 16 of 16   previous << 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Privacy | Disclaimer | Sitemap | Terms of Use
Copyright © Twenty First Century International Fire Equipment - all rights reserved
Website designed by Dark Horse Productions